Reaction force fixing frame selection materials

Anchor bolt allowable shearing force/extraction load

Shearing strength

S= A×fs A: Bolt axial cross-section area (cm2)
A= π×d2 d: Bolt axial diameter (cm). In the case of M12, d=1.2
4 fs: Bolt momentary allowable shearing stress intensity
fs=10.1kN/cm2

Bolt name Axial cross-section area A(cm2) Allowable shearing force S(kN)
M10 0.785 7.93
M12 1.13 11.42
M16 2.01 20.3
M20 3.141 31.73

Extraction strength

Allowable extraction load of post-construction metallic expansion anchor bolt
(external thread type)

Typical floor slab upper surface

Typical floor slab upper surface

Momentary allowable extraction load(kN)

Bolt diameter
d name
Concrete thickness(mm) Embedded length L
(mm)
120 150 180 220
M8 3.00 3.00 3.00 3.00 40
M10 3.80 3.80 3.80 3.80 45
M12 6.70 6.70 6.70 6.70 60
M16 9.20 9.20 9.20 9.20 70
M20 12.0 12.0 12.0 12.0 90
M24 12.0 12.0 12.0 12.0 100
Bolt embedded length
L limit(mm)
100 or less 120 or less 160 or less 180 or less
    Note
  • 1. The above diagram shows the momentary allowable extraction load when anchor bolts of the lengths in the above table are embedded.
  • 2.Concrete design standard strength Fe is given as 1.8kN/cm4 (18N/mm2).
  • 3.When the various dimensions differ from the above diagram or the concrete design standard strength varies, the calculation shall be that of a solid foundation. However, anchor bolts installed on a floor slab upper surface shall not be able to bear an extraction load of more than 12.0kN each.
  • 4. It is preferable to not use bolts with an embedded length less than in the column on the right.
  • 5.Be sure to allow a buffer of approximately 10% in selection when Type 1 and Type 2 Lightweight Concrete are used.

Typical ceiling slab lower surface and concrete wall surface

Typical ceiling slab lower surface and concrete wall surface

Prolonged allowable extraction load(kN)

Bolt diameter
dname
Concrete thickness(mm) Embedded length L
(mm)
120 150 180 220
M8 2.00 2.00 2.00 2.00 40
M10 2.50 2.50 2.50 2.50 45
M12 4.50 4.50 4.50 4.50 60
M16 6.10 6.10 6.10 6.10 70
M20 8.0 8.0 8.0 8.0 90
M24 8.0 8.0 8.0 8.0 100
Bolt embedded length
L limit(mm)
100 or less 120 or less 160 or less 180 or less
    Note
  • 1.The above diagram shows the prolonged allowable extraction load when anchor bolts of the lengths in the above table are embedded.
  • 2.Concrete design standard strength Fe is given as 1.8kN/cm2 (18N/mm2).
  • 3.When the various dimensions differ from the above diagram or the concrete design standard strength varies, the calculation shall be that of the solid foundation above, and the value obtained divided by 1.5 shall be the allowable extraction load. However, anchor bolts installed on ceiling slab lower surfaces and concrete wall surfaces shall not be able to bear an extraction load of more than 8.0kN each.
  • 4.It is preferable to not use bolts with an embedded length less than in the column on the right.
  • 5.It is also necessary to consider the momentary extraction load due to earthquakes for heavy objects with supports on typical ceiling slab lower surfaces and concrete wall surfaces. With regard to this momentary extraction load, the momentary allowable extraction load in item b) must also be considered.
  • 6.Be sure to allow a buffer of approximately 10% in selection when Type 1 and Type 2 Lightweight Concrete are used.

Refer to: Building Installed Equipment Earthquake‐Resistant Design and Installation Guidelines (FY 2005 edition), editorial supervision by The Building Center of Japan
/National Institute for Land and Infrastructure Management, Ministry of Land, Infrastructure, Transport and Tourism/Building Research Institute

Example of selection table for anchor bolts and materials used in a fixing frame (H=750mm or less) (1)

Floor fixing frame

Floor fixing frame
Seismic isolation
joint reaction
force(P)
Dimensions(mm) Materials used Floor fixing
anchor bolts
Ceiling fixing
anchor bolts
H L Equal angle steel Size Number of
pieces
Size Number of
pieces
200
(kgf)
250 300 L-40×40×5 M12 4 M12 4
500 L-40×40×5 M12 4 M12 4
1000 L-40×40×5 M12 4 M12 4
500 300 L-40×40×5 M12 4 M12 4
500 L-40×40×5 M12 4 M12 4
1000 L-40×40×5 M12 4 M12 4
750 300 L-40×40×5 M12 4 M12 4
500 L-40×40×5 M12 4 M12 4
1000 L-40×40×5 M12 4 M12 4
500
(kgf)
250 300 L-40×40×5 M12 4 M16 4
500 L-40×40×5 M12 4 M12 4
1000 L-50×50×6 M12 4 M12 4
500 300 L-40×40×5 M16 4 M12 8
500 L-40×40×5 M12 4 M12 4
1000 L-50×50×6 M12 4 M12 4
750 300 L-50×50×4 M20 4 M16 8
500 L-50×50×4 M12 4 M16 4
1000 L-50×50×6 M12 4 M12 4
1000
(kgf)
250 300 L-40×40×5 M20 4 M16 8
500 L-50×50×6 M12 4 M16 4
1000 L-65×65×6 M12 4 M12 4
500 300 L-50×50×6 M16 8
500 L-50×50×6 M16 4 M12 8
1000 L-65×65×6 M12 4 M12 4
750 300 L-65×65×6 M20 8
500 L-65×65×6 M20 4 M16 8
1000 L-65×65×6 M12 4 M16 4
1500
(kgf)
250 300 L-50×50×4 M16 8 M20 8
500 L-65×65×6 M16 4 M20 4
1000 L-75×75×6 M12 4 M12 4
500 500 L-65×65×6 M12 8 M16 8
1000 L-75×75×6 M12 4 M16 4
750 500 L-65×65×6 M16 8
1000 L-75×75×6 M16 4 M20 4

As there are no anchor bolts compatible with the items marked * in the table, it is necessary to increase the width (L dimension) of the frame.

Ceiling fixing frame

Ceiling fixing frame
Seismic isolation
joint reaction
force(P)
Dimensions(mm) Materials used Floor fixing anchor bolts Ceiling fixing anchor bolts
H L Equal
angle steel
Size Number
of pieces
Size Number
of pieces
2000
(kgf)
250 300 L-50×50×6 M20 8
500 L-65×65×6 M20 4 M16 8
1000 L-75×75×9 M12 4 M12 4
500 500 L-65×65×6 M16 8
1000 L-75×75×9 M16 4 M20 4
750 500 L-65×65×6 M20 8
1000 L-75×75×9 M20 4 M16 8
2500
(kgf)
250 500 L-75×75×6 M12 8 M20 8
1000 L-90×90×7 M12 4 M16 4
500 500 L-75×75×6 M20 8
1000 L-90×90×7 M16 4 M16 8
750 1000 L-90×90×7 M12 8 M20 8
3000
(kgf)
250 500 L-75×75×6 M16 8 M20 8
1000 L-100×100×7 M12 4 M20 4
500 1000 L-100×100×7 M20 4 M20 8
750 1000 L-100×100×7 M16 8 M20 8

As there are no anchor bolts compatible with the items marked * in the table, it is necessary to increase the width (L dimension) of the frame.

Materials used in a fixing frame (H=1,000mm- no more than 2,000mm) Example of selection table for anchor bolts (2)

Floor fixing frame

Floor fixing frame
Seismic
isolation joint
reaction force(P)
Dimensions(mm) Column and beam components Brace components Anchor bolts
H L Equal angle steel Equal angle steel Size Number of pieces
200
(kgf)
1000 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
1250 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
1500 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
2000 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
500
(kgf)
1000 500 L-40×40×5 L-40×40×3 M16 4
1000 L-50×50×6 L-40×40×3 M12 4
1250 500 L-40×40×5 L-40×40×3 M16 4
1000 L-50×50×6 L-40×40×3 M12 4
1500 500 L-40×40×5 L-40×40×3 M20 4
1000 L-50×50×6 L-40×40×3 M12 4
2000 500 L-50×50×6 L-40×40×3 M20 4
1000 L-50×50×6 L-40×40×3 M12 4
1000
(kgf)
1000 500 L-50×50×6 L-40×40×3 M16 8
1000 L-65×65×6 L-40×40×3 M12 4
1250 500 L-50×50×6 L-40×40×3 M16 8
1000 L-65×65×6 L-40×40×3 M16 4
1500 500 L-50×50×6 L-40×40×3 M20 8
1000 L-65×65×6 L-40×40×3 M16 4
2000 500 L-65×65×6 L-40×40×3 M16 16
1000 L-65×65×6 L-40×40×3 M20 4
1500
(kgf)
1000 500 L-65×65×6 L-40×40×3 M20 8
1000 L-75×75×6 L-40×40×3 M20 4
1250 500 L-65×65×6 L-40×40×3 M12 16
1000 L-75×75×6 L-40×40×3 M20 4
1500 500 L-65×65×6 L-40×40×3 M16 16
1000 L-75×75×6 L-40×40×3 M16 8
2000 500 L-65×65×6 L-40×40×3 M20 16
1000 L-75×75×6 L-40×40×3 M16 8
2000(kgf) 1000 500 L-75×75×6 L-40×40×3 M16 16
1000 L-75×75×9 L-40×40×3 M12 8
1250 500 L-75×75×6 L-40×40×3 M16 16
1000 L-75×75×9 L-40×40×3 M16 8
1500 500 L-75×75×6 L-40×40×3 M20 16
1000 L-75×75×9 L-40×40×3 M16 8
2000 500 L-75×75×6 L-40×40×3
1000 L-75×75×9 L-40×40×3 M20 8
2500
(kgf)
1000 500 L-75×75×9 L-40×40×3 M16 16
1000 L-90×90×7 L-40×40×3 M16 8
1250 500 L-75×75×9 L-40×40×3 M20 16
1000 L-90×90×7 L-40×40×3 M20 8
1500 500 L-75×75×9 L-40×40×3
1000 L-90×90×7 L-40×40×3 M20 8
2000 500 L-75×75×9 L-40×40×3
1000 L-90×90×7 L-40×40×3 M16 16
3000
(kgf)
1000 500 L-90×90×7 L-40×40×3 M20 16
1000 L-100×100×7 L-40×40×3 M20 8
1250 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3 M20 8
1500 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3 M16 16
2000 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3 M16 16

As there are no anchor bolts compatible with the items marked * in the table, it is necessary to increase the width (L dimension) of the frame.

Materials used in a fixing frame (H=1,000mm- no more than 2,000mm) Example of selection table for anchor bolts(3)

Ceiling fixing frame

Ceiling fixing frame
Seismic
isolation
joint reaction
force(P)
Dimensions(mm) Column and beam components Brace components Anchor bolts
H L Equal angle steel Equal angle steel Size Number of pieces
200
(kgf)
1000 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
1250 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
1500 500 L-40×40×5 L-40×40×3 M12 4
1000 L-40×40×5 L-40×40×3 M12 4
2000 500 L-40×40×5 L-40×40×3 M16 4
1000 L-40×40×5 L-40×40×3 M12 4
500
(kgf)
1000 500 L-40×40×5 L-40×40×3 M20 4
1000 L-50×50×6 L-40×40×3 M12 4
1250 500 L-40×40×5 L-40×40×3 M12 8
1000 L-50×50×6 L-40×40×3 M12 4
1500 500 L-40×40×5 L-40×40×3 M16 8
1000 L-50×50×6 L-40×40×3 M16 4
2000 500 L-50×50×6 L-40×40×3 M20 8
1000 L-50×50×6 L-40×40×3 M16 4
1000
(kgf)
1000 500 L-50×50×6 L-40×40×3 M20 8
1000 L-65×65×6 L-40×40×3 M20 4
1250 500 L-50×50×6 L-40×40×3 M12 16
1000 L-65×65×6 L-40×40×3 M20 4
1500 500 L-50×50×6 L-40×40×3 M16 16
1000 L-65×65×6 L-40×40×3 M16 8
2000 500 L-65×65×6 L-40×40×3 M20 16
1000 L-65×65×6 L-40×40×3 M16 8
1500
(kgf)
1000 500 L-65×65×6 L-40×40×3 M16 16
1000 L-75×75×6 L-40×40×3 M16 8
1250 500 L-65×65×6 L-40×40×3 M20 16
1000 L-75×75×6 L-40×40×3 M16 8
1500 500 L-65×65×6 L-40×40×3 M20 16
1000 L-75×75×6 L-40×40×3 M20 8
2000 500 L-65×65×6 L-40×40×3
1000 L-75×75×6 L-40×40×3 M12 16
2000
(kgf)
1000 500 L-75×75×6 L-40×40×3 M20 16
1000 L-75×75×9 L-40×40×3 M20 8
1250 500 L-75×75×6 L-40×40×3
1000 L-75×75×9 L-40×40×3 M20 8
1500 500 L-75×75×6 L-40×40×3
1000 L-75×75×9 L-40×40×3 M16 16
2000 500 L-75×75×6 L-40×40×3
1000 L-75×75×9 L-40×40×3 M16 16
2500
(kgf)
1000 500 L-75×75×9 L-40×40×3
1000 L-90×90×7 L-40×40×3 M20 8
1250 500 L-75×75×9 L-40×40×3
1000 L-90×90×7 L-40×40×3 M16 16
1500 500 L-75×75×9 L-40×40×3
1000 L-90×90×7 L-40×40×3 M16 16
2000 500 L-75×75×9 L-40×40×3
1000 L-90×90×7 L-40×40×3 M20 16
3000
(kgf)
1000 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3 M16 16
1250 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3 M16 16
1500 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3 M20 16
2000 500 L-90×90×7 L-40×40×3
1000 L-100×100×7 L-40×40×3

As there are no anchor bolts compatible with the items marked * in the table, it is necessary to increase the width (L dimension) of the frame.